Lift controller MLC 8000
Operating manual V2.0
2
EAF9
8 connected inputs / outputs of FVE (E9-E16 and A9-A16
0V switching)
Connector 2 (EAF9) is connected with the onboard buzzer of TVE
3
EAF10
4
EAF11
5
EAF12
6
EAF13
7
EAF14
8
EAF15
9
EAF16
10
+24A
Battery buffered 24V power
11
+24V
+24V power
12
GND
0V power
13
+24V
+24V power
14
NL
Emergency light car operation panel COP (output A7 FVE)
15
+24A
Battery buffered 24V power
16
M
Intercom microphone
17
L
Intercom loudspeaker
18
CH+
CAN-Bus – High signal
19
CH-
CAN-Bus – Low signal
20
GND
0V power
XT7
Flat cable connection to FVE Version 1.1 (Connector XF4) or to connect to car call boards
with flat cable connection (Fa. KLST)
1
NR
Alarm call car operation panel COP
2
EAF10
7 connected inputs / outputs of FVE (E10-E16 and A10-A16
0V switching)
3
EAF11
4
EAF12
5
EAF13
6
EAF14
7
EAF15
8
EAF16
9
0(24V)
0V power
10
+24V
+24V power
11
NL
Emergency light car operation panel COP (output A7 FVE)
12
+24A
Battery buffered 24V power
13
M
Intercom microphone
14
L
Intercom loudspeaker
XT8
Slot 1 for connecting a UEA to power supply and CAN bus
XT9
Slot 1 for connecting a UEA to power supply and CAN bus
BZ1
Buzzer
KT1
Alarm call relay
Characteristics and features:
Distribution board and emergency light for use in car operation panel COP
- 24 white LED for area-wide lighting of emergency light window in car operation panel COP
- electric buzzer for use as overload signal, door close signal and / or car call acknowledgement (set
by parameter); if flat cable is used as connection to FVE the buzzer ist connected to output AF9 of
FVE.
- Alarm call relay with potential-free changeover contact
- Slots for connecting the UEA boards
- Connector for handheld terminal
Technical specifications: