The DPV1 command channel
DPV1 command 55dec (37hex):
read current AS-i slave lists
11-60
Example:
Word no.
Value [hex]
Description
1 076F
07 = reflected user ID 7
6F = command status is "ready" (no fault)
2
0037
37 = reflected command number 55
3 0102
LAS slaves 1(A) to 15(A):
0102
hex
= 0000 0001 0000 0010
2
slaves 1 and 8 are active
4 8001
LAS slaves 16(A) to 31(A):
8001
hex
= 1000 0000 0000 0001
2
slaves 16(A) and 31(A) are active
5 0102
LAS slaves 1B to 15B:
0102
hex
= 0000 0001 0000 0010
2
slaves 1B and 8B are active
6 8001
LAS slaves 16B to 31B:
8001
hex
= 1000 0000 0000 0001
bin
slaves 16B and 31B are active
7 0102
LDS slaves 0 to 15(A):
0102
hex
= 0000 0001 0000 0010
bin
slaves 1(A) and 8(A) are detected
8 8001
LDS slaves 16(A) to 31(A):
8001
hex
= 1000 0000 0000 0001
bin
slaves 16(A) and 31(A) are detected
9 0102
LDS slaves 1B to 15B:
0102
hex
= 0000 0001 0000 0010
bin
slaves 1B and 8B are detected
10 8001
LDS slaves 16B to 31B:
8001
hex
= 1000 0000 0000 0001
bin
slaves 16B and 31B are detected
11 0100
LPF slaves 0 to 15(A):
0100
hex
= 0000 0001 0000 0000
bin
periphery fault on slave 8(A) signalled
12 0001
LPF slaves 16(A) to 31(A):
periphery fault on slave 16(A) signalled
13 0002
LPF slaves 1B to 15B:
periphery fault on slave 1B signalled
14 8000
LPF slaves 16B to 31B:
8000
hex
= 1000 0000 0000 0000
bin
periphery fault on slave 31B signalled
15 0102
LPS slaves 1(A) to 15(A):
0102
hex
= 0000 0001 0000 0010
bin
slaves 1(A) and 8(A) are projected
16 8001
LPS slaves 16(A) to 31(A):
8001
hex
= 1000 0000 0000 0001
bin
slaves 16(A) and 31(A) are projected
17 0102
LPS slaves 1B to 15B:
0102
hex
= 0000 0001 0000 0010
bin
slaves 1B and 8B are projected
18 8001
LPS slaves 16B to 31B:
8001
hex
= 1000 0000 0000 0001
bin
slaves 16B and 31B are projected
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...