The DPV1 command channel
DPV1 command 31dec (1Fhex):
one-time execution of the "Extended safety monitor protocol" in the "Safety at Work" monitor
11-29
Description of the different fields:
Word no. 4:
LEDs OSSD 1
LEDs OSSD 2
15
14
13
12
11
10
9
8
Description
0 0 0 0 0 0 0 0
green:
contacts
of the output circuits closed
0
0
0
1
0
0
0
1
yellow: startup / restart disable active
0 0 1 0 0 0 1 0
yellow flashing or
red: contacts of the output circuits open
0 0 1 1 0 0 1 1
red flashing: error on the level of the monitored AS-i
components
0 1 x x 0 1 x x
reserved
(x = any value)
data call 1
data call 0
7
6
5
4
3
2
1
0
Description
0 0 0 0 0 0 0 0
protective operation; everything OK
(output circuits which are not available, not configured or
dependent are indicated as OK)
0
0
0
1
0
0
0
1
protective operation, output circuit 1 off
0
0
1
0
0
0
1
0
protective operation, output circuit 2 off
0
0
1
1
0
0
1
1
protective operation, both output circuits off
0 1 0 0 0 1 0 0
configuration
operation:
power
on
0 1 0 1 0 1 0 1
configuration
operation
0
1
1
0
0
1
1
0
not reserved / not defined
0 1 1 1 0 1 1 1
configuration operation: fatal device error, RESET or
replacement of devices required
no current diagnosis information available, please wait
Word no. 5:
OSSD2 not green
OSSD1 not green
15…12
11
10...8
7…4
3
2...0
Description
reserved 0 0 reserved 0
0
no module - responses of the data calls in the words 6..17 are
not relevant
reserved
0
1...6
reserved
0
1...6
number of modules which are not green
reserved
0
7
reserved
0
7
more than 6 modules are not green
Word no. 6...17:
1st to 6th module address output circuit 1/2:
Indicates the index of the module of the configuration. The module address which was defined in the
program ASIMON is indicated.
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...