DP module 12: Extended command channel
Module 12, extended command 105dec (69hex):
read the device properties of the controllere
9-72
0
bin
device with 1 AS-i master
2M
1
bin
device with 2 AS-i masters
0
bin
fieldbus interface Profibus DP(V1) not available
DP
1
bin
fieldbus interface Profibus DP is available
0
bin
device without Ethernet programming interface
EN
1
bin
device without Ethernet programming interface
01
hex
PLC is in the RUN mode
02
hex
PLC is in the STOP mode
04
hex
PLC stops at the breakpoint
PLC mode
08
hex
gateway mode
01
hex
Anybus Profibus DP
04
hex
Anybus CANopen
05
hex
Anybus DeviceNet
09
hex
Anybus Ethernet IT
0A
hex
Anybus Ethernet/IP
0B
hex
ifm Profibus DP
fieldbus
type
0C
hex
no fieldbus module detected
Example:
Word no.
Value [hex]
Description
1 0669
06 = reflected user ID changes e.g. to 6,
69 = reflected command number 105
2 0000
reserved
3 4008
40
hex
= 0100 0000
bin
2M = 0
→
with one AS-i master,
DP = 1
→
Profibus DP controllere,
EN = 0
→
without Ethernet programming interface,
PLC mode 08
hex
= gateway; signal preprocessing is not used
4
000B
0B = fieldbus interface "ifm Profibus DP" used
5
0002
flash memory type
6 1000
hardware
version
7 0002
1
st
part of the RTS firmware number 02.218B:
RTS firmware version number = 02
8 218B
2
nd
part of the RTS firmware number 02.218B:
RTS firmware release number = 218B
9 0000
1
st
part of the firmware number 0.238A for AS-i master 1:
AS-i master 1 firmware version number = 0
10 238A
2
nd
part of the firmware number 0.238A for AS-i master 1:
AS-i master 1 firmware release number = 238A
11 0000
1
st
part of the firmware number 0.238A for AS-i master 2:
AS-i master 2 firmware version number = 0
12 238A
2
nd
part of the firmware number 0.238A for AS-i master 2:
AS-i master 2 firmware release number = 238A
13 0196
Linux kernel version:
0196
hex
= 406
dec
14 0A6E
Linux ramdisk version:
0A.6E
hex
= 10.110
dec
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...