DP module 12: Extended command channel
Module 12, extended command 31dec (1Fhex):
one-time execution of the "Extended safety monitor protocol" in the "Safety at work" monitor
9-33
1st to 6th colour output circuit 1/2:
3
2
1
0
Description
0 0 0 0
green,
continuous
0 0 0 1
green,
flashing
0 0 1 0
yellow,
continuous
0 0 1 1
yellow,
flashing
0 1 0 0
red,
continuous
0 1 0 1
red,
flashing
0 1 1 0
grey,
off
Example ("Safety at work" monitor has not switched):
Word no.
Value [hex]
Description
1 071F
07 = reflected user ID 7
1F = reflected command number 31
2 0000
reserved
3 001E
00 = reflected sub command 0
1E = AS-i slave address 30
4
0000
green: contacts of the output circuits closed
5
0000
both output circuits green
6…17
xxxx
not relevant because 5th word = 0000
18
0100
field number = 1
Example ("Safety at work" monitor has switched):
Word no.
Value [hex]
Description
1 071F
07 = reflected user ID 7
1F = reflected command number 31
2 0000
reserved
3 001E
00 = reflected sub command 0
1E = AS-i slave address 30
4 0211
0xxx = output circuit 2 green
x2xx = output circuit 1 red;
→
word 5
xx11 = protective operation, output circuit 1 off (in both data calls)
5 0003
result from 4th word = OSSD2 green; OSSD1 not green
03 = provides 3 modules which are not green
6
0421
module 33 (21) red, continuous (04)
7
0422
module 34 (22) red, continuous (04)
8
0423
module 35 (23) red, continuous (04)
9…11 xxxx
not relevant because low byte of 5th word = 03
→
3 modules relevant
12…17 xxxx
not relevant, because high byte of 5th word = 00: green
→
no module relevant
18
0100
field number = 1
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...