DP module 12: Extended command channel
Module 12, acyclic command 38dec (26hex):
manufacturer-specific read call of an AS-i slave with CTT2 profile
(S-7.5.5, S-7.A.5 or S-B.A.5)
9-47
9.23
Module 12, acyclic command 38
dec
(26
hex
):
manufacturer-specific read call of an AS-i slave with CTT2 profile
(S-7.5.5, S-7.A.5 or S-B.A.5)
– available from master profile M4 onwards –
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R
S
0/1
M
0/1
user ID
command number = 26
hex
= 38
dec
2
R R
A/B
0/1
slave address
reserved = 0
3
number of bytes to be read
Index
4…18
not used
Legend
→
page
and
Index
Pointer to the page to be read
Length: 1 byte
Permitted values: 0…255
dec
(0…FF
hex
)
Description:
→
data sheet of the addressed CTT2 slave
Number of
bytes to be
read
Number of bytes to be read
Length: 1 byte
Permitted values: 1…32
dec
(01…20
hex
)
Description:
→
data sheet of the addressed CTT2 slave
Example:
Word no.
Value [hex]
Description
1 0626
M=0: AS-i master 1
06 = user ID changes e.g. to 6
26 = command number 38
2
0300
03 = slave address 3(A)
3
0409
in index 9, 4 parameter bytes are to be read
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...