Additional functions
AS-i diagnosis via Profibus DP
12-3
12.1.4
Diagnostic master flags (byte 10 / byte 36)
Format of the first byte of the diagnostic master flags, so for byte 10 (AS-i master 1) and byte 36 (AS-i
master 2):
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
CTRL Cerr Offl PF APF Sl0 ProjM
WdRS232
Legend
CTRL
controllere PLC in the operating mode RUN
Cerr
AS-i configuration error
Offl
AS-i master offline (no AS-i slave detected)
PF
AS-i periphery fault
APF
AS-i voltage fault
Sl0
AS-i slave with address 0 detected
ProjM
AS-i master in the operating mode projecting
WdRS232
watchdog triggered by the interface RS-232C of the controllere
Format of the slave lists:
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0(A)
15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A)
23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)
31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A)
7B 6B 5B 4B 3B 2B 1B
res.*)
15B 14B 13B 12B 11B 10B 9B 8B
23B 22B 21B 20B 19B 18B 17B 16B
31B 30B 29B 28B 27B 26B 25B 24B
*) slave address 0B is not allowed
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...