Set-up
Parameter setting of the Profibus host
7-11
7.3.2
Assign PLC addresses to the Profibus modules
What are "Profibus modules"? These are entries in a parameter setting database of the programming
software for the Profibus DP master system (host). There you assign the individual "modules" to the
virtual "locations".
Locations are address areas for certain functions.
Modules are placeholders for certain address quantities within these areas.
The following IEC addresses are the designations for the PLC addresses in the controllere:
IEC address area
from
to
Description
Data flow
AS-i host
DP module
%IB1.1
%IB1.31
master 1, slaves 1A...31A, digital inputs
→
1 input
%IB2.1
%IB2.31
master 2, slaves 1A...31A, digital inputs
→
2 inputs
%IB11.1
%IB11.31
master 1, slaves 1B...31B, digital inputs
→
3 input
%IB12.1
%IB12.31
master 2, slaves 1B...31B, digital inputs
→
4 input
%IW21.1.x %IW21.31.x
master 1, slaves 1...31,
analogue inputs x = channel*)
→
5 and 10
%IW22.1.x %IW22.31.x
master 2, slaves 1...31,
analogue inputs x = channel *)
→
5 and 10
%IW0.0 %IW0.63
DP
outputs
for signal preprocessing
←
9
%IB0.128 %IB0.143
DP outputs for master1, slaves 1A...31A,
digital outputs
←
1 output
%IB0.144 %IB0.159
DP outputs for master1, slaves 1B...31B,
digital outputs
←
3 output
%IB0.160 %IB0.175
DP outputs for master2, slaves 1A...31A,
digital outputs
←
2 output
%IB0.176 %IB0.191
DP outputs for master 2, slaves 1B...31B,
digital outputs
←
4 output
%IW0.96 %IW0.219
DP outputs for master 1, slaves 1...31,
analogue outputs
←
11
%IW0.224 %IW0.347
DP outputs for master 2, slaves 1...31,
analogue outputs
←
11
%IB0.704 %IB0.719
DP parameters for master 1, slaves
1A...31A, parameter data
←
DP
parameters
%IB0.720 %IB0.735
DP parameters for master 1, slaves
1B...31B, parameter data
←
DP
parameters
%IB0.736 %IB0.751
DP parameters for master 2, slaves
1A...31A, parameter data
←
DP
parameters
%IB0.752 %IB0.767
DP parameters for master 2, slaves
1B...31B, parameter data
←
DP
parameters
%QB1.1 %QB1.31
master 1, slaves 1A...31A,
digital outputs
→
–
%QB2.1 %QB2.31
master 2, slaves 1A...31A,
digital outputs
→
–
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...