The DPV1 command channel
DPV1 command 6dec (06hex):
readdress a connected AS-i slave
11-14
Response from controllere (DPV1 slave) in case of an error
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
command status = 6B
hex
2
00
reflected command number = 06
hex
3
ignored error
code
Example:
Word no.
Value [hex]
Description
1 086B
08 = reflected user ID changes e.g. to 8
6B = error during command execution
2
0006
06 = reflected command number 6
3 0003
error code 03
hex
→
slave with address 0 connected
Possible error codes
Error code
Name
Description
01 NOK
no slave response or:
master is in the offline mode when calling the command
02
SND
no slave with the old address found
03
SD0
slave with address 0 connected
04
SD2
no slave with the new address found
05
DE
error when deleting the old address
06
RE
error when reading the IO configuration
07
SE
error when writing the new address or the extended ID code 1
08
AT
new address could only be saved temporarily
09
ET
extended ID code 1 could only be saved temporarily
0B
ID
parameter or address invalid
14
IC
master is not in the normal mode
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...