DP module 7: Command channel
Module 7, command 8:
read LAS (list of active slaves)
8-9
8.9
Module 7, command 8:
read LAS (list of active slaves)
Slave group
The 2 feedback bytes can only give information about max. 16 slaves. Therefore the slaves are
divided in 4 groups (
→
following table).
When querying the slave lists any slave number from the requested slave group is to be indicated.
Byte 3
Byte 4
Bit
Group
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
1
15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0
*
2
31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)
3
15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B res
4
31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B
*) LAS and LPS have no slave 0, therefore this bit is set to 0!
Structure
Request of DP master
Bit
MM = master no. (1…2)
Byte
7
6
5
4
3
2
1
0
1
0 0
08
hex
X = slave type (0…1)
0 = standard / A slave
1 = B slave
2
MM X
SSSSS
SSSSS = slave no. (0…31
dec
)
3
0
not used *)
4
0
not used *)
Response from controllere
Bit
Byte
7
6
5
4
3
2
1
0
1
D7 D6
08
hex
2
copy of the request
D6 = command code
D7 = error code
→
page
, table at the bottom
3
→
table above
4
→
table above
provides the addresses of the active slaves in this address
group
*)
IMPORTANT:
For the query read only the required bytes. Unused bytes can contain information of
previous queries.
Example
→
next page
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...