DP module 12: Extended command channel
Module 12, extended command 105dec (69hex):
read the device properties of the controllere
9-71
9.38
Module 12, extended command 105
dec
(69
hex
):
read the device properties of the controllere
Request of DP master:
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R
R
R
user ID
command number = 69
hex
= 105
dec
2…18
not used
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0669
06 = user ID changes e.g. to 6,
69 = command number 105
Response from controllere (gateway)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0 B=0 R
reflected user ID
reflected command number = 69
hex
2
reserved = 0
reserved = 0
3
2M DP EN
reserved
PLC
mode
4
0 fieldbus
type
5
0
flash memory type
6
hardware version
7
RTS firmware version number
8
RTS firmware release number
9
AS-i master 1 firmware version number
10
AS-i master 1 firmware release number
11
AS-i master 2 firmware version number
12
AS-i master 2 firmware release number
13
Linux kernel version
14
Linux ramdisk version
15…18
reserved
Legend
→
page
and
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...