DP module 7: Command channel
Module 7, command 21dec (15hex):
save configuration in flash
8-19
8.18
Module 7, command 21
dec
(15
hex
):
save configuration in flash
Structure
Request of DP master
Bit
MM = master no. (1…2)
Byte
7
6
5
4
3
2
1
0
1
0 0
15
hex
2
MM 0
3
0
not used *)
4
0
not used *)
Response from controllere
Bit
Byte
7
6
5
4
3
2
1
0
1
D7 D6
15
hex
2
copy of the request
D6 = command code
D7 = error code
→
page
, table at the bottom
3
0
not used *)
4
0
not used *)
Example: Save AS-i configuration in flash for AS-i master 1
Request of DP master
Byte no.
Value [hex]
Description
1
15
15 = command 21
2 40
(master no.
1 * 64
)
= 64
dec
=
40
hex
3
00
not used *)
4
00
not used *)
Response from controllere
Byte no.
Value [hex]
Description
1
15
copy of the request
2
40
copy of the request
3
00
not used *)
4
00
not used *)
*)
IMPORTANT:
For the query read only the required bytes. Unused bytes can contain information of
previous queries.
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...