DP module 12: Extended command channel
Module 12, extended command 10...20dec (0A...14hex):
force analogue data transfer directly to / from 3 AS-i slaves in each case
9-20
9.13
Module 12, extended command 10...20
dec
(0A...14
hex
):
force analogue data transfer directly to / from 3 AS-i slaves in each
case
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R R
M
0/1
user ID
command number = 0A...14
hex
= 10...20
dec
2
reserved = 0
reserved = 0
3
output data AS-i slave 1(A), channel 0
4
output data AS-i slave 1(A), channel 1
5
output data AS-i slave 1, channel 2 or
output data AS-i slave 1B, channel 0
6
output data AS-i slave 1, channel 3 or
output data AS-i slave 1B, channel 1
7
reserved = 0
O3 V3 O2 V2 O1 V1 O0 V0
8
output data AS-i slave 2(A), channel 0
9
output data AS-i slave 2(A), channel 1
10
output data AS-i slave 2, channel 2 or
output data AS-i slave 2B, channel 0
11
output data AS-i slave 2, channel 3 or
output data AS-i slave 2B, channel 1
12
reserved = 0
O3 V3 O2 V2 O1 V1 O0 V0
13
output data AS-i slave 3(A), channel 0
14
output data AS-i slave 3(A), channel 1
15
output data AS-i slave 3, channel 2 or
output data AS-i slave 3B, channel 0
16
output data AS-i slave 3, channel 3 or
output data AS-i slave 3B, channel 1
17
reserved = 0
O3 V3 O2 V2 O1 V1 O0 V0
18
not used
Legend
→
page
and
V0…V3 Valid
Vx=0: data invalid
Vx=1: data valid
Output data must be valid (V=1) to be enabled in the AS-i slave!
O0...O3 Overflow
Ox=0: data are in the valid range
Ox=1: data are in the invalid range
(especially in case of input modules, when the measuring range is not reached or exceeded)
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...