The DPV1 command channel
DPV1 command 10...20dec (0A...14hex):
force analogue data transfer directly to / from 3 AS-i slaves in each case
11-19
Example:
Word no.
Value [hex]
Description
1 0165
01 = user ID changes e.g. to 1
65 = command request
2
000A
0A = DPV1 command number 10
3
0169
output data AS-i slave 1, channel 0
4
0202
output data AS-i slave 1, channel 1
5
0395
output data AS-i slave 1, channel 2
6
1033
output data AS-i slave 1, channel 3
7 0055
overflow and valid bits for AS-i slave 1:
55
hex
= 0101 0101
bin
O3 = 0, V3 = 1, O2 = 0, V2 = 1, O1 = 0, V1 = 1, O0 = 0, V0 = 1
8
2009
output data AS-i slave 2, channel 0
9
2202
output data AS-i slave 2, channel 1
10
0195
output data AS-i slave 2, channel 2
11
1022
output data AS-i slave 2, channel 3
12 0055
overflow and valid bits for AS-i slave 2:
55
hex
= 0101 0101
bin
O3 = 0, V3 = 1, O2 = 0, V2 = 1, O1 = 0, V1 = 1, O0 = 0, V0 = 1
13
3339
output data AS-i slave 3, channel 0
14
1102
output data AS-i slave 3, channel 1
15
1953
output data AS-i slave 3, channel 2
16
1234
output data AS-i slave 3, channel 3
17 0055
overflow and valid bits for AS-i slave 3:
55
hex
= 0101 0101
bin
O3 = 0, V3 = 1, O2 = 0, V2 = 1, O1 = 0, V1 = 1, O0 = 0, V0 = 1
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...