The DPV1 command channel
DPV1 command 28dec (1Chex):
deactivate the slave reset when changing to the protected mode
11-26
11.13
DPV1 command 28
dec
(1C
hex
):
deactivate the slave reset when changing to the protected mode
Request of DPV1 master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
user ID
command request = 65
hex
2
00
command number = 1C
hex
= 28
dec
3
ignored
with / without offline phase
4…19
ignored
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0465
04 = user ID changes e.g. to 4
65 = command request
2
001C
1C = command number 28
3 0001
offline phase when changing over to the protected mode:
00 = YES
→
slave reset
01 = NO
→
no slave reset
Response from controllere (DPV1 slave)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
command status = 6F
hex
2
00
reflected command number = 1C
hex
Example:
Word no.
Value [hex]
Description
1 046F
04 = reflected user ID 4
6F = command status is "ready" (no fault)
2
001C
1C = reflected command number 28
Содержание Ecomat 300 AC1355
Страница 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Страница 12: ...On this manual Overview where is what 1 4 ...
Страница 14: ...Safety instructions Functions and features 2 2 ...
Страница 16: ...System requirements Required accessories 3 2 ...
Страница 18: ...Getting started Set up Profibus DPV1 4 2 ...
Страница 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Страница 52: ...Set up Finish set up 7 28 ...
Страница 76: ...DP module 7 Command channel Module 7 command 63dec 3Fhex no operation command without function 8 24 ...
Страница 226: ...The DPV1 command channel DPV1 command 105dec 69hex read the device properties of the controllere 11 72 ...
Страница 238: ...Technical data Profibus DP interface 13 2 ...
Страница 246: ...Terms abbreviations 15 6 ...
Страница 248: ...Index 16 2 System Save parameters 12 10 Target 15 5 TFR Register 14 2 Troubleshooting 14 1 Watchdog 15 5 ...