d.
Select
Display Disk Configuration
, and then press Enter.
e.
Select
Display non-configured units
, and then press Enter. Is the failed drive a non-configured
unit?
v
No: Continue to 6
v
Yes: Continue to 4.
f.
Determine whether the disk drive or solid-state drive to be removed was replaced by a hot-spare
drive when it failed. An
xxxx9031
error that was logged close to the same time as the original
disk failure indicates that the data to the hot-spare drive was automatically rebuilt.
4.
Determine whether the disk drive or solid-state drive to be removed was replaced by a hot-spare
drive when it failed. Complete the following steps:
a.
Go to the service action log. For instructions to access the service action log, see “Activating the
failing-part indicator light” on page 135
b.
Determine whether an
xxxx9031
error was logged close to the same time as the original disk
failure. This error indicates that the data to the hot-spare drive was automatically rebuilt.
c.
Determine whether an error was logged for the field-replaceable unit (FRU) by using concurrent
maintenance. If yes, continue with the next step.
5.
Did you find the service action log entry related to this problem?
v
No
: Exit the service action log and go to step 7
v
Yes
: Continue with the next step.
6.
Within the service action log, select the concurrent maintenance option. This option displays the
drive location on the concurrent maintenance display. Go to step 9 on page 43
7.
From the Hardware Service Manager, navigate to
Select Device Concurrent Maintenance
option.
Press Enter. The Device Concurrent Maintenance display is shown, as shown in the following figure.
Device Concurrent Maintenance
Type the choices, then press Enter.
Specify either physical location or resource name.
Physical location:
U787A.001.1234567-P3-D4
or
Device resource name:
Specify action as 1=Remove device
2=Install device
Action to be performed . . . . . . . .: 1
Enter a time value between 00 and 19.
Time delay needed in minutes . . . . .: 01
F3=Exit
F5=Refresh
F12=Cancel
Figure 26. Example Device Concurrent Maintenance display
42
Disk drives or solid-state drives
Содержание 8248-L4T
Страница 1: ...Power Systems Disk drives or solid state drives for the 8248 L4T 8408 E8D or 9109 RMD...
Страница 2: ......
Страница 3: ...Power Systems Disk drives or solid state drives for the 8248 L4T 8408 E8D or 9109 RMD...
Страница 10: ...viii Disk drives or solid state drives...
Страница 18: ...2 Disk drives or solid state drives...
Страница 70: ...54 Disk drives or solid state drives...
Страница 90: ...74 Disk drives or solid state drives...
Страница 94: ...78 Disk drives or solid state drives...
Страница 98: ...82 Disk drives or solid state drives...
Страница 142: ...126 Disk drives or solid state drives...
Страница 144: ...128 Disk drives or solid state drives...
Страница 148: ...132 Disk drives or solid state drives...
Страница 158: ...142 Disk drives or solid state drives...
Страница 162: ...146 Disk drives or solid state drives...
Страница 198: ...182 Disk drives or solid state drives...
Страница 202: ...186 Disk drives or solid state drives...
Страница 212: ...196 Disk drives or solid state drives...
Страница 213: ......
Страница 214: ...Printed in USA...