Chapter 2 Wiring
49
[2] Port Number Assignment for I/O Ports
With the following I/O parameters, assign the ranges and numbers of the ports used on PIO
board.
No.
Parameter Name
Default
(Reference)
Input Range
Remarks
1 I/O Port Assignment Type
0
(Reference
value)
0 to 20
0: Fixed assignment (No other than 0 can be set)
2
Input Port Start Number at
I/O1 Affixed Assignment
000
-1, 0 to 248
0+(multiple of 8)(Unavailable when it is negative
figure)
3
Standard
Output Port Start Number
at I/O1 Affixed Assignment
300
-1, 300 to 548
300+(multiple of 8)(Unavailable when it is negative
figure)
16
Input Port Start Number at
I/O2 Affixed Assignment
-1
-1, 0 to 288
0+(multiple of 8)(Unavailable when it is negative
figure)
17
Output Port Start Number
at I/O2 Affixed Assignment
-1
-1, 300 to 588
300+(multiple of 8)(Unavailable when it is negative
figure)
18
I/O2 Error Monitoring
1
0 to 1
0: Not to Monitor (The extension not applicable)
1: Monitor (Use the extension)
225
Extension
Extension I/O Controller
9
(Reference
value)
0 to 9
0 to 8:Extension not installed or other than PIO
installed
9:PIO (Extension installed)
283
Input Function Select 000
Physical Input Port No.
16
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 30 (Input port 000 when negative)
284
Input Function Select 001
Physical Input Port No.
17
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 31 (Input port 001 when negative)
285
Input Function Select 002
Physical Input Port No.
18
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 32 (Input port 002 when negative)
286
Input Function Select 003
Physical Input Port No.
19
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 33 (Input port 003 when negative)
287
Input Function Select 004
Physical Input Port No.
20
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 34 (Input port 004 when negative)
288
Input Function Select 005
Physical Input Port No.
21
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 35 (Input port 005 when negative)
289
Input Function Select 006
Physical Input Port No.
22
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 36 (Input port 006 when negative)
290
Input Function Select 007
Physical Input Port No.
23
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 37 (Input port 007 when negative)
291
Input Function Select 008
Physical Input Port No.
24
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 38 (Input port 008 when negative)
292
Input Function Select 009
Physical Input Port No.
25
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 39 (Input port 009 when negative)
293
Input Function Select 010
Physical Input Port No.
26
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 40 (Input port 010 when negative)
294
Input Function Select 011
Physical Input Port No.
27
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 41 (Input port 011 when negative)
295
Input Function Select 012
Physical Input Port No.
28
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 42 (Input port 012 when negative)
296
Input Function Select 013
Physical Input Port No.
29
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 43 (Input port 013 when negative)
297
Input Function Select 014
Physical Input Port No.
30
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 44 (Input port 014 when negative)
298
Input Function Select 015
Physical Input Port No.
31
-1, 16 to 31,
48 to 299
Indicate port number to assign function set in I/O
Parameter No. 45 (Input port 015 when negative)
299
Output Function Select 300
Physical Input Port No.
316
0, 316 to 331,
348 to 599
Indicate port number to assign function set in I/O
Parameter No. 46 (Output port 301 when 0)
300
Output Function Select 301
Physical Input Port No.
317
0, 316 to 331,
348 to 599
Indicate port number to assign function set in I/O
Parameter No. 47 (Output port 302 when 0)
301
Output Function Select 302
Physical Input Port No.
318
0, 316 to 331,
348 to 599
Indicate port number to assign function set in I/O
Parameter No. 48 (Output port 303 when 0)
302
Output Function Select 303
Physical Input Port No.
319
0, 316 to 331,
348 to 599
Indicate port number to assign function set in I/O
Parameter No. 49 (Output port 304 when 0)
303
Output Function Select 304
Physical Input Port No.
320
0, 316 to 331,
348 to 599
Indicate port number to assign function set in I/O
Parameter No. 50 (Output port 305 when 0)
304
Output Function Select 305
Physical Input Port No.
321
0, 316 to 331,
348 to 599
Indicate port number to assign function set in I/O
Parameter No. 51 (Output port 306 when 0)