Chapter 5 I/O Parameter
148
5.10.14 Want to Reset Errors Externally
Errors other than cold-start level errors are reset when input port 029 is turned ON (errors are
reset at the OFF
ON edge).
Parameter No.
Set Value
Description
I/O parameter No.43
2
Set input port 013 as the error reset signal
input port
(
When I/O Parameter No. 296 = 29
)
5.10.15 Want to Change Input Port Assignments
You can select input functions by I/O parameter Nos. 30 to 45 and assign them to desired
input ports.
Parameter No.
Set Value
Description
I/O parameter No.283
Input port number to
assign input function
selection 000 to
I/O parameter No.284
Input port number to
assign input function
selection 001 to
I/O parameter No.297
Input port number to
assign input function
selection 014 to
I/O parameter No.298
Input port number to
assign input function
selection 015 to
Explanation below shows how to assign Input Function Select 000 “Start” set in “Input
Function Select 000” to another input port.
Set the physical input port number of Input Function Select 000 (Start) in I/O Parameter No.
283 “Input Function Select 000 Physical Input Port Number”. For instance, when “016” is set,
the function of Input Function Select 000 (Start) is assigned to “Input Port No. 016”.
The signal input port of Input Function Select 000 (Start) becomes Input Port 016.
“Input Port No. 000” after the assignment becomes an input port for general purpose.
(Note) Even though the input port numbers can be set individually, Error No. 685 “Input and
Output Function Select Physical Port Number Error” will be generated in case a
duplicated setting is made or port number setting is made not in a continuous order.