10 Alarm List
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
203
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Cause
Solution
0338
PDC output
breaker open
Critical
The output
circuit breaker
on the PDC is
OFF.
1.
Check that all UPS output circuit
breakers are ON.
2.
On the LCD, check that
PDC output
breaker open
alarm has disappeared. If
the alarm persists, tap the
Clear Fault
button to clear the alarm.
0341
PDC Maint.
breaker closed
Minor
The maintenance
circuit breaker
on the PDC is
ON.
The running status is displayed. No further
measures are required.
0342
Mains input
breaker open
Critical
The mains input
circuit breaker is
OFF.
The running status is displayed. No further
measures are required.
0343
BPM input
breaker open
Critical
The bypass input
circuit breaker is
OFF.
The running status is displayed. No further
measures are required.
0340
Maint. breaker
closed
Minor
The maintenance
circuit breaker is
ON.
The running status is displayed. No further
measures are required.
0335
Generator
connected
Warning
The generator is
connected.
The running status is displayed. No further
measures are required.
0594-1
Insufficient
redundant
racks
Minor
The load is
excessive.
The
configured
number of
redundant
racks is
incorrect.
1.
Reduce the load.
2.
Decrease the configured number of
redundant racks.
0095-1
Insuffi.
redundancy
Minor
The load is
excessive.
The
configured
number of
redundant
modules is
incorrect.
1.
Reduce the load.
2.
Decrease the configured number of
redundant modules.
0096-1
ECO volt.
Abnormal
Minor
The ECO
bypass
voltage or
frequency is
out of the
preset range.
1.
Check the bypass input voltage and
frequency.
2.
Check that the rated voltage, rated
frequency, ECO bypass voltage range,
and frequency range are correctly set.
3.
Check that the bypass cables and circuit