UPS5000-S-1200 kVA
User Manual
4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
105
Table 4-15
Bitwise AND operation example
-
PC IP Address
(182.98.225.125)
UPS IP Address
(182.98.225.112)
PC IP address/UPS IP
address
10110110.01100010.111000
01.01111101
10110110.01100010.111000
01.01110000
Subnet mask
(255.255.255.192)
11111111.11111111.111111
11.11000000
11111111.11111111.111111
11.11000000
Bitwise AND operation
result
10110110.01100010.111000
01.01000000
10110110.01100010.111000
01.01000000
−
Automatic
: The MDU automatically searches for available IP addresses in the
connected network. Ensure that the MDU and PC are on the same network segment.
After you restart the device,
IP address allocation
changes back to
Manual
. The IP address is set to the
IP address set previously.
Item
Description
Default Value Value Range
IP address
Specifies the IP address for the
Ethernet.
NOTICE
Ensure that the UPS IP address is
unique on the network segment.
Otherwise, the WebUI display
function may not function properly.
192.168.0.10
1.0.0.0–223.255.
255.255
Subnet mask
Specifies the subnet mask of the
Ethernet.
255.255.255.0
0.0.0.0–255.255.
255.255
Gateway
Specifies the Ethernet gateway.
192.168.0.1
1.0.0.0–223.255.
255.255
NAT mapping
NAT means network address
translation. If it is set to
Disable
,
Internet cannot access IP
addresses in the local area
network (LAN).
Disable
Disable, Enable