UPS5000-S-1200 kVA
User Manual
3 Installation
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
67
Figure 3-36
Installing the busbar covers
Step 9
Before power-on, remove the protective covers from the top of the power units.
Figure 3-37
Removing the protective covers
----End
3.2.5 Installing Optional Components
3.2.5.1 Installing a Battery Grounding Failure Detector
Prerequisites
If the power units share battery strings, you need to install a battery grounding failure
detector only in power unit 1.
If the power units do not share battery strings, you need to install battery grounding
failure detectors in both power units.