UPS5000-S-1200 kVA
User Manual
8 Technical Specifications
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
191
Item
Specifications
THDi ≤ 5% (full non-linear load)
Table 8-5
Bypass input electrical specifications
Item
Specifications
System
Three-phase, four-wire, and PE
Rated voltage
380 V AC/400 V AC/415 V AC (line voltage)
Rated frequency
50/60 Hz
Frequency range
50/60 Hz ±6 Hz (adjustable with the tolerance of 0.5–6 Hz, ±2
Hz by default)
Input mode
The mains input and bypass input share a power source or use
different power sources.
Table 8-6
Battery electrical specifications
Item
Specifications
Battery voltage
360 V DC to 600 V DC
12 V batteries, 30–50 batteries, 40 batteries by default
If there are 40 to 50 batteries, the output power is not
derated.
If there are 36 to 39 batteries, the output power is derated
to 90%.
If there are 32 to 35 batteries, the output power is derated
to 80%.
If there are 30 to 31 batteries, the output power is derated
to 70%.
2 V batteries, 180–300 batteries, 240 batteries by default
If there are 240 to 300 batteries, the output power is not
derated.
If there are 239 to 216 batteries, the output power is
derated to 90%.
If there are 215 to 192 batteries, the output power is
derated to 80%.
If there are 191 to 180 batteries, the output power is
derated to 70%.
Battery management
Intelligent battery management
Cold start by pressing one
button
If a mains outage occurs, batteries can start the UPS to supply
power to loads.
Charger output power
Under rated conditions, the maximum charge power of a