UPS5000-S-1200 kVA
User Manual
3 Installation
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
46
Table 3-3
Power cable terminal requirements
Port
Descriptio
n
Connection
Method
Bolt
Specificatio
ns
Bolt Length
Torque
Mains input
Crimped DT
terminals
M12
35 mm
47 N·m
Bypass
input
Crimped DT
terminals
M12
35 mm
47 N·m
Battery
input
Crimped DT
terminals
M16
55 mm
120 N·m
Output
Crimped DT
terminals
M12
35 mm
47 N·m
PE
Crimped DT
terminals
M12
35 mm
47 N·m
Equipotenti
al ground
point
Crimped DT
terminals
M6
N/A
4.5 N·m
Table 3-4
Recommended upstream input and downstream output circuit breakers
Circuit Breaker Name
Specifications
a
Mains input circuit breaker
2500 A/3P
Bypass input circuit breaker
2500 A/3P
Downstream output circuit breaker
The system has a general output switch. There is
no need to add an external circuit breaker.
a: recommended model when the short-circuit current where the circuit breaker is located is
less than 65 kA
The upstream input circuit breakers recommended in the table are for reference only.
If multiple loads are connected, specifications for branch circuit breakers must not exceed the
recommended specifications.
The circuit breaker selection principle is to protect loads and cables, and the cascading principle is to
realize specific protection.