4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
110
Figure 4-23
System settings 2
Figure 4-24
System settings 3
Item
Description
Default Value Value Range
Single/Parallel
Specifies whether the UPS works
in single mode or parallel mode.
Single
Single, Parallel
Requisite
modules
Matches the system capacity.
-
12–22
Redundant
modules
Set this parameter based on load
capacity and redundancy
requirements.
0
0–10
Working mode
UPS working mode
Normal mode
Normal mode,
ECO, Self-load
mode, Converter
mode
ECO voltage
range
In ECO mode, when the
difference between the bypass
voltage and the rated voltage is
greater than this value, the
system determines that the ECO
voltage is abnormal and transfers
±5%
±5%, ±6%, ±7%,
±8%, ±9%,
±10%