4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
99
The
Power Cabinet N
data in the system running is the same as the
Battery Info
data in the power unit
running.
Table 4-11
Total runtime
Item
Description
Bypass runtime (h)
Time for which the UPS runs in bypass mode.
Inv. runtime (h)
Time for which the UPS runs in inverter mode.
The value must be an integer. For example:
If the value is less than 1, the value takes 0.
If the value is greater than or equal to 1 and less than 2, the value takes 1.
Table 4-12
Environment data
Item
Description
Ambient temperature (°C)
Temperature measured by the ambient temperature and
humidity sensor. (An ambient temperature and humidity
sensor is required. If no sensor is connected, the ambient
temperature sampled by the bypass unit is displayed.)
Ambient humid. (%RH)
Humidity measured by the ambient temperature and
humidity sensor. If the sensor is not installed,
NA
is
displayed.
Module Data: reflects each data of a module.
Battery Detailed Data - Batt. String Data: reflects the voltage, current, SOC, and SOH
data of each battery string.
Battery Detailed Data - String N Battery Data: reflects the temperature, voltage, internal
resistance, current, SOC, and SOH data of a single battery in the battery string.
4.1.3.2 Alarms
Table 4-13
Alarm display description
Running Item
System
Power Unit
Bypass Unit
Active Alarms
All active alarms
Active alarms of this
power unit
Active alarms of the
bypass unit
Historical Alarms
All historical alarms
Historical alarms of
this power unit
Historical alarms of
the bypass unit
Buzzer Off
Buzzer off
-
-
Clear Faults
Clearing all alarms
-
-