5.6 Testing Batteries
5.6.1 Forced Equalized Charging Test
Context
Before a forced equalized charging test, ensure that:
The mains input is normal.
Batteries are properly connected.
Batteries are not in the equalized charging state.
If the battery strings of two power units are shared, you only need to perform the forced
equalized charging test for one power unit to complete all battery tests. If the battery strings
are not shared, you need to perform the forced equalized charging test on the LCD of both
power units to complete all battery tests.
Procedure
Step 1
On the home screen of the power unit LCD, choose
Power Unit N Info.
>
Maintenance
>
Battery Maint
.
Step 2
Tap
Start
next to
Forced Equalized Charging
to start a forced equalized charging test.