UPS5000-S-1200 kVA
User Manual
3 Installation
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
43
Figure 3-2
Distances between the top copper bars of the bypass unit and input and output unit
(unit: mm)
(1) The area marked by the line box is reserved for dense busway.
(2) No power distribution box (PDB) or cabling is allowed inside the area marked by the
line box.