UPS5000-S-1200 kVA
User Manual
4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
138
Item
Description
Default Value Value Range
charge current and float charge
time.
Transfer-to-equ
alized charging
cur. coef. (C10)
The battery enters equalized
charge state when the battery
current exceeds this parameter
value.
0.05
0.02–0.08
SOC to start
equalized
charging (%)
If the SOC is lower than the
specified value, batteries start
equalized charging.
70
0–100
Scheduled
equalized
charging
interval (d)
After batteries transfer from
equalized charging to float
charging, if the batteries do not
discharge, equalized charging
starts only after the float charging
time reaches
Equalized
charging protection interval
.
After equalized charging is
complete, scheduled equalized
charging starts when the
non-equalized charging time
exceeds
Scheduled equalized
charging interval
.
60
30–180
Equalized
charging
protection
interval (d)
7
0–15
Forced
equalized
charging
protection time
(h)
When batteries are continuously
under float charging or
hibernation, enable forced
equalized charging. When the
forced equalized charging time
reaches the value of this
parameter, batteries
automatically transfer to float
charging mode.
18
12–24
Max. batt. dis.
time (h)
Set the maximum battery
discharge time. When the
discharge time reaches this value,
the UPS powers off. If the time is
set to 0 hours, battery discharge
protection is not implemented.
24
0–48
EOD restart
If the mains is not functioning
normally, the UPS will transfer
to battery mode. When batteries
reach the EOD threshold, the
bypass is disabled, and
EOD
restart
is
Enable
, the UPS will
restart as soon as the mains
resumes.
If
EOD restart
is disabled, clear
the alarm manually or enable the
restart function for the UPS.
Enable
Disable, Enable