UPS5000-S-1200 kVA
User Manual
4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
140
Item
Description
Default Value Value Range
than the warning threshold.
Intelligent
hibernation
If this parameter is set to
Enable
,
the intelligent battery hibernation
function is enabled.
Disable
Disable, Enable
Thres. of low
batt. SOC over
dry contact (%)
If an output dry contact is set to
Low battery SOC
, and the
battery SOC is lower than this
threshold, the output dry contact
will output signals.
75
5–80
Thres. of low
batt. volt. over
dry contact
(V/cell)
If an output dry contact is set to
Batt. Volt. Below Threshold
,
and the battery voltage is lower
than this threshold, the output dry
contact will output signals.
1.70
1.70–2.10
4.2.2.2 Communication Settings
Figure 4-49
System communication settings
Figure 4-50
Power unit communication settings