10 Alarm List
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
198
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Cause
Solution
faulty.
The dry
contact board
is faulty.
is available, check on the dry contact
board whether the battery grounding
failure detector is enabled. If yes,
disable it and check whether the alarm is
cleared. If the alarm persists, the dry
contact board may be faulty. Replace the
board.
0032-1
Battery
overvoltage
protection
Critical
The battery
voltage is
greater than
the upper
threshold.
The
configured
number of
batteries is
less than the
actual
number.
The actual
number of
batteries does
not meet
requirements.
1.
Check the battery voltage.
2.
Check that the configured number of
batteries matches the actual number.
3.
Check that the actual number of
batteries meets requirements.
0036-2
Battery
maintenance
reminder
Warning
The time for
maintenance
arrives.
Maintain the batteries.
0037-1
Battery
undervoltage
Critical
The UPS has
worked in
battery mode
for an
extended
amount of
time.
The charger
is faulty.
1.
Check whether the battery voltage is
normal.
2.
Check whether the output is overloaded.
3.
Check whether any battery is damaged.
If yes, replace the battery.
4.
Check whether any battery charger
generates an alarm. If yes, replace the
faulty module.
0040-7
Rectifier
abnormal
Critical
The fan for
the power
module is not
functioning
properly.
The air
channel for
the power
module is
obstructed.
1.
Check that the air channel for the
module is free from blockage.
2.
Check whether the fans are functioning
properly. Replace the power module if
the fans are faulty.