UPS5000-S-1200 kVA
User Manual
10 Alarm List
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
201
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Cause
Solution
excessive.
0583-1
Inter-rack par.
cable
abnormal
Critical
The
inter-rack
parallel
system CAN
bus is
disconnected
or
short-circuite
d.
Only one
rack works in
a parallel
system.
An ECM is
faulty.
1.
Check the inter-rack parallel system
CAN bus.
2.
Rectify the disconnection or
short-circuit fault.
3.
Replace the ECM.
0583-4
The inter-rack
industrial
frequency
synchronization
cable is broken.
Replace the inter-rack parallel cable.
0583-5
The inter-rack
carrier
synchronization
cable is broken.
0583-6
The
intra-rack
INVBYP
cable is
broken.
The parallel
CAN bus is
broken.
0584-2
Inter-rack par.
cable alarm
Minor
The inter-rack
parallel cable is
faulty.
Replace the inter-rack parallel cable.
0584-4
The inter-rack
industrial
frequency
synchronization
cable is broken.
0085-1
EPO
Critical
The EPO button
is pressed.
Restore the EPO button status. Start the
UPS after the alarm is cleared.