UPS5000-S-1200 kVA
User Manual
4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
155
Managing the UPS by Using the NMS
Applying for Access Rights
To manage the UPS by using the UNMS II of Generex over the MDU, apply to the
system administrator of the MDU for access rights and add the NMS information to the
NMS access list of the MDU. The NMS address and access right settings are used for
adding information about the NMS accessing the MDU, including the NMS address,
access right, and Trap port. For details about how to add an NMS over a web browser,
see
Figure 4-69
Setting the SNMP Trap
Managing the UPS
Take the UNMS II of Generex for example. The method for managing the UPS by using
the UNMS II is the same as the method for managing other devices by using the UNMS
II. For details, see the UNMS II user manual.
4.2.5 Protecting the Server by Using the RCCMD Software
4.2.5.1 Introduction to the Software
The RCCMD shutdown software is part of the centralized monitoring system of the Generex
network. The UPS5000 MDU integrates the functions of the Generex RCCMD server:
Sends the shutdown command, notification message, and Trap message to the RCCMD
client if the UPS system generates an alarm; executes commands on the RCCMD client.
Receives the message "UPS alive check" sent by the RCCMD client and replies with the
system status.
Configures and saves the address and port for receiving the shutdown command, and the
message sending mechanism.
For the method of installing the RCCMD client, see the manual related to the RCCMD.