Figure 5-4
Starting the inverter
If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or you perform shutdown or rectify faults) and the module can be started, the module
responds to the startup command.
----End
5.1.4 Powering On Loads
Context
After the inverter starts, the UPS works in normal mode. The
Bypass mode
alarm disappears.
Procedure
Step 1
After confirming that the battery strings are properly connected, close the battery string input
circuit breaker. If there are multiple battery strings, close the circuit breaker for each battery
string and then the general circuit breaker between battery strings and the UPS. The
No
battery
alarm disappears from the MDU.
Step 2
Turn on the system output switch (Q5) to supply power to loads.
----End
5.1.5 (Optional) Setting Parameters for the BCB Box
Prerequisites
A BCB box is installed.
If the power units share battery strings, you need to set BCB box parameters only on the
LCD of power unit 1.
If the power units do not share battery strings, you need to set BCB box parameters on
the LCD of both power units.