4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
134
Item
Description
Default Value Value Range
RAM
verification
Enable or disable the memory
check function. If this parameter
is set to
Enable
, the control chip
RAM working status is checked
regularly. If this parameter is set
to
Disable
, regular check is
disabled.
Disable
Disable, Enable
Record time
after fault
Indicates the time for storing
fault data after the UPS
experiences a fault. The default
value is 0 ms, which means that
the data during 20 ms before the
fault occurs is recorded. If the
value is set to 40 ms, it means
that the data during 20 ms before
the fault occurs and the data
during 40 ms after the fault
occurs are recorded, and the like.
0 ms
0 ms, 20 ms, 40
ms, 60 ms, 80
ms
Collect
real-time site
waveform
If this parameter is set to
Enable
,
one waveform can be stored
manually.
Disable
Disable, Enable
Fan life
Indicates the life detection for
fans in the power modules and
bypass module.
Enable
Disable, Enable
Pre-warn. time
for fan life
(mon)
Indicates the time when a
warning about fan life needs to
be raised in advance before the
fan life ends.
12
1–24
Input Settings
Item
Description
Default Value Value Range
Input
adaptability
The value of
Input adaptability
can be
Strong
or
Weak
. Strong
input adaptability applies to the
D.G. or input sources whose
input current has high frequency
oscillation. In this mode, the total
distortion of the input current
waveform (THDi) is poor, but
the system is stable. Weak input
adaptability is suitable for mains
and AC input sources.
Strong
Strong, Weak