UPS5000-S-1200 kVA
User Manual
2 Overview
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
21
Indicator
Color
Status
Description
FPGA software is being upgraded
(blinking at 4 Hz, on for 0.125s
and off for 0.125s).
Off
The rectifier FPGA software is
being upgraded.
Alarm indicator
Yellow
Steady on
A minor alarm is generated for the
inverter or rectifier.
Off
There is no minor alarm for the
inverter or rectifier, or the rectifier
FPGA software is being upgraded.
Fault indicator
Red
Steady on
A critical alarm is generated for
the inverter or rectifier.
Off
There is no critical alarm for the
inverter or rectifier, or the rectifier
FPGA software is being upgraded.
Functions
The power module consists of a power factor correction (PFC) rectifier, inverter, and DC/DC
converter. The power module performs AC/DC or DC/DC conversion on the mains and
battery inputs, and stabilizes the bus voltage. The inverter (DC/AC) converts the inputs into
sine wave outputs.
Specifications
Dimensions (H x W x D): 130 mm x 442 mm x 620 mm
Weight: < 34 kg
Rated output capacity: 55 kVA/55 kW