UPS5000-S-1200 kVA
User Manual
10 Alarm List
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
200
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Cause
Solution
bypass input circuit breaker 10 seconds
later.
0564-1
Overload
timeout
Critical
The load is
excessive.
Derating
reduces the
rated system
power.
The module
is damaged.
The output is
incorrectly
grounded.
1.
Check that there is no overload.
2.
Check that the module power is not
derated due to a fan fault.
3.
Check whether the power grid has a
large asymmetric load.
4.
Check whether the output is grounded.
5.
If the alarm persists, replace the power
module.
0565-1
Load impact
transfer-to-byp
ass
Minor
A
large-power
RCD load is
instantly
connected, or
the output
load
short-circuits.
The inverter
bridge
short-circuits.
1.
Check the load.
2.
If the load is normal, replace the power
module.
0566-1
Output
overload
Minor
The load is
excessive.
Derating
reduces the
rated system
power.
The module
is damaged.
1.
Check that there is no overload.
2.
Check that the module power is not
derated due to a fan fault.
3.
If the alarm persists, replace the power
module.
0570-4
BPM module
abnormal
Critical
The bypass
fan is not
functioning
properly, or
the air
channel is
blocked.
The ambient
temperature
exceeds the
upper
threshold.
The load is
1.
Check the bypass fan and air channel. If
the fan is faulty, replace it.
2.
Check that the ambient temperature has
not exceeded 40°C.
3.
Check that there is no overload.