UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
5 Operations
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
136
Set
Single/Parallel
after double check. Incorrect settings may affect the normal UPS
operation.
Output voltage level
refers to the line voltage level. Set it based on site requirements.
Set
Output frequency
correctly. Otherwise, loads may be affected and the UPS may not
work properly.
Set all battery parameters correctly based on site requirements. Battery parameter settings
are critical to battery maintenance, battery lifespan, and UPS discharge time.
Figure 5-1
Settings Wizard
Set the time and date correctly. Incorrect time and date will cause false fault analysis during
maintenance or repair, affecting the normal operation.
After network parameters are set, connect the UPS to the network, ensuring that maintenance
personnel can manage or control the UPS remotely. If you do not need remote management, retain
the default network parameter settings.
Step 2
After you set parameters on the
Settings Wizard
screen, the system displays the
Bypass
mode
and
No battery
alarms, which do not need to be handled. Other alarms need to be
handled.