UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
B Alarm List
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
169
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Possible Cause Suggestion
The dry
contact card
is faulty.
card whether the battery grounding
failure detector is enabled. If yes,
disable it and check whether the alarm is
cleared. If the alarm persists, the dry
contact card may be faulty. Replace the
card.
0032-1
Battery
overvoltage
protection
Critical
The battery
voltage is
greater than
the upper
threshold.
The
configured
number of
batteries is
less than the
actual
number.
The actual
number of
batteries does
not meet
requirements.
1.
Check the battery voltage.
2.
Check that the configured number of
batteries matches the actual number.
3.
Check that the actual number of
batteries meets requirements.
0036-2
Battery
maintenance
reminder
Warning
The batteries are
due for
maintenance.
Maintain the batteries.
0037-1
Battery
undervoltage
Critical
The UPS
works in
battery mode
for a long
time.
The charger
is faulty.
1.
Check that the battery voltage is normal.
2.
Check that the output is not overloaded.
3.
Check whether any battery is damaged.
If yes, replace the faulty battery.
4.
Check whether any alarm is generated
for a battery charger. If a charger is
damaged, replace the related module.
0040-7
Rectifier
abnormal
Critical
The fans of
the power
module are
abnormal.
The
ventilation
channel of
the power
module is
obstructed.
1.
Check whether the ventilation channel
of the power module is blocked. If yes,
rectify the fault to restore the normal
operation of the fans.
2.
Check whether the fans are abnormal.
Replace the power module if the fans
are faulty.
0043-1
Fan abnormal
Critical
The fans of
the power
Replace the faulty power module.