UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
8 Technical Specifications
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
162
Item
Specifications
30–40°C: not derated at 342–485 V AC, derated from 100%
load to 45% load at 342–191 V AC, and derated from 45%
load to 35% load at 191–139 V AC
Rated frequency
50 Hz/60 Hz
Frequency range
40–70 Hz
Power factor
> 0.99 (100% load)
> 0.98 (50% load)
> 0.94 (30% load)
Harmonic current
THDi < 9% (30% linear load), THDi < 6% (50% linear
load), THDi < 3% (100% linear load)
THDi < 11% (30% non-linear load), THDi < 8% (50%
non-linear load), THDi < 5% (100% non-linear load)
Table 8-6
Bypass input electrical specifications
Item
Specifications
Power system
Three-phase four-wire + PE
Rated voltage
380 V AC/400 V AC/415 V AC (line voltage)
Rated frequency
50 Hz/60 Hz
Frequency range
50 Hz/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6 Hz,
±2 Hz by default)
Input mode
The mains input and bypass input share a power source (by
default) or use different power sources.
Table 8-7
Battery electrical specifications
Item
Specifications
Battery voltage (VRLA
battery)
360–600 V DC
12 V batteries (30–50 batteries optional, 0 by default; set
based on site requirements)
2 V batteries (180–300 batteries optional, 0 by default; set
based on site requirements)
Battery cold start
If a mains outage occurs, batteries can start the UPS to supply
power to loads.
Charger output power
Under rated conditions, the maximum charge power of a
module is 15 kW, and the charge current is limited to 30 A.
Battery string sharing
(VRLA battery)
Supported in a parallel system