UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
4 User Interface
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
123
4.2.3 Monitoring
Figure 4-46
Monitoring
Item
Description
UPS System
View
Running Information
of the UPS, set
Running Parameter
for the
UPS, and perform
Running Control
on the UPS.
Bypass
View the bypass input
Running Information
and set
Running
Parameter
.
Module
Summary
Query the module
Running Information
and set
Running Parameter
.
ECM
Summary
Set
Running Parameter
for the ECM.
Battery
System
View the battery
Running Information
and set
Running Parameter
.
Battery String
Summary
NOTE
If
Number of iBOXs
is not
0
and lead-acid batteries are used,
Battery String
Summary
is displayed on the
Monitoring
page.
Set parameters for the iBOX and iBAT connected to each battery string.
UPS System
Table 4-12
System settings
Item
Description
Default
Value
Value Range
High ambient
temperature alarm
threshold(°C)
An alarm is generated when the ambient
temperature reaches or exceeds the threshold
specified by this parameter.
55
40–60
Low ambient
temperature alarm
threshold(°C)
An alarm is generated when the ambient
temperature is lower than the threshold specified
by this parameter.
–10
–20 to 0
EPO detection
Specifies whether to enable EPO. EPO is
performed only when this parameter is enabled
and the EPO switch is triggered.
When
EPO detection
is changed from
Disable
Disable
Disable, Enable