UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
B Alarm List
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
170
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Possible Cause Suggestion
module are
abnormal.
The fan
monitoring
cable for the
power
module is
abnormal.
0043-2
The fans are
faulty.
Check the fans or replace the bypass
module.
0043-3
The fans are
faulty.
The fan
monitoring
cable is
faulty.
1.
Replace the fans.
2.
Check the fan monitoring cable.
0043-4
0047-1
Not ready
Critical
The ready switch
is OFF.
Turn on the ready switch.
0060-4
Inverter
abnormal
Critical
A load short
circuit
occurs.
A short
circuit occurs
inside the
module (this
fault seldom
occurs).
The output is
incorrectly
grounded.
1.
Check load cable connections.
2.
Check that the output is grounded.
3.
If the load cable connections are normal
and the output is correctly grounded,
replace the power unit or module.
0061-2
Inverter alarm
Minor
The I2C bus
is abnormal.
The
E2PROM is
faulty.
1.
Manually rectify the fault and check
whether the alarm is cleared.
2.
If the alarm is generated again, replace
the power module.
0061-7
Inverter alarm
Minor
The bypass
waveform is
abnormal.
If not all modules generate the alarm,
start the UPS, transfer it to inverter
mode, and replace the modules that
generate the alarm.
If all modules generate the alarm, switch
off the bypass input circuit breaker.
After the inverter relay is closed, switch
on the bypass input circuit breaker 10s