UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
4 User Interface
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
111
Dry contact extended card (MUE07A): currently provides five input and five output
signals.
Item
Description
MUE05A connection
Specifies the MUE05A connection status. Independent
input signals can be enabled only when this parameter
is set to
Enable
.
Battery ground fault [BTG]
Specifies whether to enable or disable battery
grounding fault detection.
D.G. connection [GEN]
Specifies whether to enable or disable DG connection
status detection.
BCB connection [OL]
Specifies whether to enable or disable BCB connection
status detection.
Battery breaker [STA]
Specifies whether to enable or disable battery circuit
breaker status detection.
PDC output breaker [OUT]
Specifies whether to enable or disable PDC output
circuit breaker status detection.
PDC maintenance breaker [MT]
Specifies whether to enable or disable PDC
maintenance circuit breaker status detection.
BP/SYSMT switch
If the BP/SYSMT switch is set to
Enable
, the port has
dry contact signal access. How to use the port depends
on the status of the BP/SYSMT switch.
BP/SYSMT switch function
If the BP/SYSMT switch is set to
Enable
, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is used to
detect the status of the PDC bypass input circuit
breaker or system maintenance circuit breaker.
SPD/SYSOUT switch
If the SPD/SYSOUT switch is set to
Enable
, the port
has dry contact signal access. How to use the port
depends on the status of the SPD/SYSOUT switch.
SPD/SYSOUT switch function
If the SPD/SYSOUT switch is set to
Enable
, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is used to
detect the status of the PDC input SPD or system
output circuit breaker.
MUE06A connection
Specifies the MUE06A connection status. The mains
and bypass backfeed protection is enabled only when
this parameter is set to
Enable
.
MUS05A DO_1 Action,
MUS05A DO_2 Action,
MUS05A DO_3 Action,
MUS05A DO_4 Action
Controls the status of DO ports on the MUS05A dry
contact card.
MUE07A DO_1 Action,
MUE07A DO_2 Action,
MUE07A DO_3 Action,
Controls the status of DO ports on the MUE07A dry
contact extended card.