UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
B Alarm List
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
174
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Possible Cause Suggestion
0337
PDC bypass
input breaker
open
Critical
The bypass input
circuit breaker of
the PDC is OFF.
The running status is displayed. No further
measures are required.
0338
PDC output
breaker open
Critical
The output
circuit breaker of
the PDC is OFF.
1.
Check that all UPS output circuit
breakers are ON.
2.
On the LCD, check whether PDC output
breaker open alarm has disappeared. If
no, tap the
Clear Fault
button to clear
the alarm.
0341
PDC Maint.
breaker closed
Minor
The PDC
maintenance
circuit breaker is
ON.
The running status is displayed. No further
measures are required.
0342
Mains input
breaker open
Critical
The mains input
circuit breaker is
OFF.
The running status is displayed. No further
measures are required.
0343
BPM input
breaker open
Critical
The bypass input
circuit breaker is
OFF.
The running status is displayed. No further
measures are required.
0340
Maint. breaker
closed
Minor
The maintenance
circuit breaker is
ON.
The running status is displayed. No further
measures are required.
0335
Generator
connected
Warning
The generator is
connected.
The running status is displayed. No further
measures are required.
0594-1
Insufficient
redundant
racks
Minor
The loads are
excessive.
The
configured
number of
redundant
racks is
incorrect.
1.
Reduce the loads.
2.
Decrease the configured number of
redundant racks.
0095-1
Insuffi.
redundancy
Minor
The loads are
excessive.
The
configured
number of
redundant
modules is
incorrect.
1.
Reduce the loads.
2.
Decrease the configured number of
redundant modules.
0096-1
ECO volt.
Abnormal
Minor
The ECO
bypass
voltage or
1.
Check the bypass input voltage and
frequency.
2.
Check that the rated voltage, rated