UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
5 Operations
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
143
Before setting ECO mode, ensure that the bypass is working properly.
Procedure
Step 1
On the LCD, choose
System Info
>
Settings
>
System Settings
and set
Working mode
to
ECO
. The information indicating that the UPS works in ECO mode is displayed on the LCD.
Step 2
Set the ECO voltage range.
Figure 5-7
ECO specifications
Step 3
(Optional) If you set ECO mode in bypass mode, manually start the UPS inverter.
After the inverter is started, the UPS still works in bypass mode, and the inverter is on standby.
When the bypass is abnormal, the UPS transfers to inverter mode immediately. If the inverter
is not started, the UPS stops supplying power when the bypass is abnormal, and the system
may power off.
Figure 5-8
System status in ECO mode
----End