UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
2 Overview
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
29
Indicator
Color
Status
Description
Off
The software is being upgraded.
Alarm
indicator
Yellow Steady
on
A minor alarm is generated for the inverter or
rectifier.
Off
There is no minor alarm for the inverter or rectifier, or
the software is being upgraded.
Fault
indicator
Red
Steady
on
A critical alarm is generated for the inverter or
rectifier.
Off
There is no critical alarm for the inverter or rectifier,
or the software is being upgraded.
Functions
The main power module consists of a power factor correction (PFC) rectifier and inverter. It
performs AC/DC or DC/DC conversion on the mains and battery inputs, and stabilizes the bus
voltage. The inverter (DC/AC) converts the inputs into sine wave outputs.
Specifications
Dimensions (H x W x D): 130 mm x 442 mm x 750 mm
Weight: < 55 kg
Rated output capacity: 100 kVA/100 kW