UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
4 User Interface
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
117
Item
Description
Internal
resistanc
e
Allows you to measure the battery internal resistance. If the condition for
measuring internal resistance is met (batteries are fully charged), you can tap
Measure
to start measuring the internal resistance of the selected iBAT in an
iBOX.
NOTE
The interval between two measurement operations must be greater than 10 minutes.
Bus Capacitor Life Estimate
If the service life of a capacitor is about to end, that is,
Module X bus capacitor life (y)
is
less than 1.0, contact Huawei technical support to replace the power module.
Wizard Startup
The wizard startup can be used to test the bypass, mains inverter, inverter/bypass switch,
battery inverter, battery charging capability, battery switch tripping, and other functions.
Perform operations as prompted.
Before performing
Wizard Startup
, ensure that: