UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
4 User Interface
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
115
Figure 4-36
Battery Maint. (lead-acid battery)
Figure 4-37
Battery Maint. (lithium battery)
Item
Description
Forced Equalized Charging
Allows you to perform equalized charging on batteries
forcibly.
Shallow Dis. Test
Allows you to partially discharge batteries. A shallow
discharge test is conducted to test the battery loop
reliability and short-time discharge capacity when the
batteries have not been discharged for a long time.
Capacity Test
Allows you to fully discharge batteries. A deep discharge
test is conducted to obtain the battery discharge
performance data.
USB Operations
You can export
Fault Data
, and perform
Export Config.
,
Upgrade Software
,
BSP Upgrade
,
and
Import Config.
on
USB Operations
.