5 Operations
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
138
Figure 5-2
Setting internet options
Step 3
In the address box of the browser, enter https://
UPS IP address
.
Step 4
Enter the correct user name and password and click
Login
.
Step 5
On the WebUI, choose
Monitoring
>
UPS System
>
Running Control
, and click
Inv. ON
,
and confirm the operation to start the inverter.
Figure 5-3
Starting the inverter
If the power module receives a startup command when it cannot be started, the startup command will be
retained for 1 minute. Within 1 minute, if there is no situation (for example, the power module
encounters other faults, executes a shutdown command, or a fault is rectified) that requires the startup
command to be cleared and the power module becomes able to start, then the power module responds to
the startup command.
----End
5.1.4 Powering On Loads
Context
After the inverter starts, the UPS transfers to inverter mode, and the
Bypass mode
alarm on
the MDU disappears.