UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
4 User Interface
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
126
Item
Description
Default
Value
Value Range
recovery
is set to
Enable
, the bus
overvoltage alarm is automatically cleared,
and the rectifier and inverter automatically
start when the bus voltage recovers (less than
420 V) within
Bus overvolt. recovery time
.
When
Bus overvoltage recovery
is set to
Disable
, the bus overvoltage alarm cannot be
automatically cleared, and the rectifier and
inverter cannot automatically start.
Bus overvolt. recovery
time
If
Bus overvoltage recovery
is set to
Enable
,
the bus overvoltage alarm is automatically
cleared, and the rectifier and inverter
automatically start when the bus voltage
recovers (less than 420 V) within
Bus
overvolt. recovery time
.
5s
5s, 1min, 5min,
10min
Capacitor failure
detection
If this parameter is set to
Enable
, the inverter
capacitor fault detection is performed based
on the settings of
Capacitor failure
detection upper limit
and
Capacitor failure
detection lower limit
. If the inverter
capacitor is faulty, the power module shuts
down the inverter to prevent the fault from
escalating.
Disable
Disable, Enable
Table 4-15
Bypass settings
Item
Description
Default
Value
Value Range
BPM mode upon BPM
overtemp.
Specifies whether to start bypass mode when
overtemperature occurs.
Enable
Disable, Enable
Battery System
Battery parameter settings are critical to battery maintenance, battery lifespan, and UPS
discharge time. When you set battery parameters, note the following: