UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
3 Installation
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
59
3.2.1 Installing a Cabinet
3.2.1.1 Installation on the Floor
Prerequisites
Ensure that the installation floor is flat.
Procedure
Step 1
Determine the cabinet installation positions on the floor based on the holes in the marking-off
template for floor installation.
A: mounting holes on the channel steel
B: mounting holes on the floor
Figure 3-6
Hole dimensions (unit: mm)
Step 2
Use a hammer drill to drill holes for installing expansion bolts and then install expansion
sleeves in the holes.